| Model | FR-320-R |
| Manufactures | Mircom |
| Origin | Canada |
| Standards | Listed to UL 864, 10th Edition and ULC-S527, 4th Edition, FM Approval |
| Standard Features | Field configurable to operate with a Deluge Sprinkler System, a Pre-action Sprinkler System and an Agent Release System |
| Six Class B (Style B) Input Circuits | |
| Input Circuits One to Four can be configured as Non-Verified Alarm, Non Latching Supervisory, Latching Supervisory or Agent Release/Water Flow depending on the Mode of Operation selected | |
| Input Circuits Five & Six can be configured as Manual Release Input, Abort Input or Abort/Manual Release Combination Input depending on the Mode of Operation selected | |
| Input Circuits can be converted to Class “A” (Style “D”) using the ICAC-306 Converter Module | |
| Four Class “B” (Style “Y”) Output Circuits which can be configured for Silenceable Signal, Non-Silenceable Signal, Silenceable Strobe, Non-Silenceable Strobe or Releasing Circuit (Circuits 3 & 4 Only) | |
| Output Circuits can be converted to Class “A” (Style “Z”) using the OCAC-304 Converter Module | |
| 5 Amp Power Supply | |
| 4-wire smoke power 22.3 VDC @ 300ma max.Supervised Aux Power 22.3 VDC @ 500ma max. | |
| Aux Power (Unregulated) 24 VDC @ 1.7 Amp max. | |
| Relay contacts for Common Alarm (Non Disconnectable), Auxiliary Alarm (Disconnectable), Common Supervisory (can be converted to common alarm if no Supervisory input) and Common Trouble | |
| Cross Zone option | |
| Counting Zones option | |
| Output signals can be configured for Steady (fixed) or Escalating (tone changes as input operation changes) | |
| Release Timer 0 to 60 Seconds (5 second increments) | |
| Manual Release Delay 0 to 30 Seconds (5 second increments) | |
| Soak Timer 0 to 15 Minutes (21 Intervals) | |
| Abort Release Timer (Standard UL Type Delay, IRL Type Delay, NYC Type Delay, Local Jurisdiction Delay) | |
| Special Releasing Power Supply and Release Activation Considerations preventing false dumps | |
| Configurable to perform two hazard areas | |
| Simple panel programming through 14 Pre-Configured Modes of Operations | |
| Dimensions | 26”H x 14.5”W x 4.2”D |