| Manufactures | Mircom |
| Origin | Canada |
| Standards | UL, FM Approval |
| Number of Loop | One addressable (SLC) loop with a maximum of 240 MGC devices (MIX-4000 series) in total. |
| Display | – 4 x 20 LCD display — 80 characters total – LED Indicators for AC On, CPU Fault, and Ground Fault |
| Standard Features | Main Board, Power Supply and Backbox |
| Flexible zones and group configuration options allowing for grouped inputs and outputs. | |
| Compatible with MGC devices (MIX-4000 Series) including photoelectric duct smoke detector and multi-modules. | |
| Device sub-addressing which saves physical address space for multi modules, sounder bases, relay bases and dual input module. | |
| Compatible with conventional detectors using MGC MIX- 4042 Conventional Zone module, refer to document LT-1023 for compatible detectors. | |
| Class A (DCLA), Class X (DCLC), or Class B (DCLB) analog loop(s). | |
| Four Power Limited Class B, Class A NAC circuits (max 1.5 Amps each – 5.0 Amps total). | |
| NAC circuits may be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or auxiliary power output. The audible signal may be Steady, Temporal Code, California Code, or March Time. | |
| Supports sync strobe protocols from major manufacturers. | |
| USB port on core board for simple programming and firmware upgrade by local keypad or PC. | |
| Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays. | |
| Additional outputs include connections for a RTI remote trouble indicator, PR-300 Reverse Polarity Module, an RS-485 bus for connection of up to seven RAX-LCD-LITEs, RAM-3318-LCDs, SRM-312s and RA-1000 Series annunciators. | |
| Built-in POTs dialer which allows for the reporting of events to a monitoring facility. The UDACT/Digital Communicator can be configured for single or dual line operation and uses the Security Industry Association (SIA) and Ademco Contact ID protocols. | |
| Full Windows 10 compatibility | |
| Bypass modules IPS-2424DS and IPS-4848DS can be used when connected to this panel as remote annunciators. These modules are mounted into a series of enclosures and connected to the RAM-3318-LCD. | |
| Two event history logs comprised of a 400 event alarm log for alarm related events and a 400 event general log for all other events | |
| Buzzer Silence can be repurposed as Auxiliary Reset | |
| The addressable devices will not flash their LEDs when no flashing flag is enabled. | |
| No Flashing flag is re-purposed to indicate the device will not flash its LED. | |
| Support 4-20mA functionality on the MIX-4042 module. | |
| Support Auto Suite Silence. | |
| Buzzer Silence can be repurposed as Auxiliary Reset. | |
| Dual relay module to operate independent relays . | |
| Group bypass switch | |
| Input Voltage | 120VAC 60Hz / 240VAC 50Hz 1.81 Amp / 0.98 Amp (primary) |
| Battery Type | 24VDC Gel Cell / Sealed lead acid |
| Operating Temperature | 32ºF to 120ºF (0ºC to 49C) |
| Humidity | 10% – 93% non-condensing |
| Dimensions | 16.7″ W x 5.7″ D x 23″ H (42.42xm x 14.48 x 58.42cm) |
| Weight (g) | Depending on the number of module on the cabinet |