| Model | FA-301-8LR |
| Manufactures | Mircom |
| Origin | Canada |
| Standards | Listed to UL 864, 10th edition and ULC-S527, 4th Edition |
| Standard Features | Available in eight zone configurations |
| Front panel (using CFG-300 configuration tool) and PC programmable | |
| Remote upload/download capabilities | |
| Base panel is equipped with Class “B” (Style “B”) initiating circuits which may be configured as Class “A” (Style “D”) using a Class “A” converter module | |
| Initiating circuits may be configured as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble-Only | |
| Base panel is equipped with Class “B” (Style “B”) indicating circuits which may be configured as Class “A” (Style “Z”) using a Class “A” signal converter module | |
| Individual disconnect buttons for both initiating and indicating circuits | |
| Audible signals may be configured for Steady, Temporal Code, California Code and March Time | |
| Indicating Circuits may be configured as Silenceable or Non-Silenceable for both signals and strobes | |
| Built-in sync protocols for the following strobe manufacturers: Mircom, Amseco, System Sensor, Gentex, Faraday and Wheelock | |
| Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble | |
| Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test | |
| Subsequent Alarm, Supervisory, and Trouble operation | |
| RS-485 Interface for Remote LED Annunciators, LCD Annunciators and Remote Smart Relay Modules | |
| Interface for a Remote Trouble Indicator (RTI) | |
| Two event history logs comprised of a 200 event alarm log for alarm related events and a 200 event general log for all other events | |
| Support i3 Series Smoke Detectors | |
| 5 Amp Power Supply | |
| Optional modules for additional internal relay circuits and City Tie/Polarity Reversal | |
| Optional trim ring for semi-flush mounting | |
| Input Voltage | 120VAC @ 60Hz / 240VAC @ 50Hz |
| Standby Power | 24VDC standby batteries |
| Charging Capability | 10 AH |
| Current Consumption Alarm | 366mA |
| Current Consumption Standby | 136mA |
| Dimensions | 26”H x 14.5”W x 4.5”D |