Features and Benefits
FN3458 (60 Hz) models of the Ecosine Flex product family represent the very compact economical series with a THDi performance of <10% for drives with 4% Ldc and <15% for drives without Ldc.
They are ideal for non-linear three-phase equipment with B6 rectifier front-end that do not require the industry leading <5% THDi performance provided by Schaffner Ecosine Evo filters.
The performance targets the requirement of EN 61000-3-12 and IEEE 519 for Isc/IL <50. Schaffner Ecosine filters help to unburden the electrical infrastructure from excess loading and heat caused by current harmonics, and therefore support a better utilization of electric system capacity.
Lower harmonics also reduce the risk of system resonances and potential downtime of sensitive electronic equipment.
FN3458 filters upgrade standard motor drives to low-harmonic drives quickly and easily.
Typical Applications
- Equipment with front-end six-pulse rectifier
- Motor drives
- Factory automation equipment
- Water/wastewater treatment facilities
- Fan and pump applications
- HVAC installations
- Mission-critical processes
Technical Specifications
Nominal operating voltage
3×380 to 480 VAC ±10%
Overload capability
1.6x rated current for 1 minute, once per hour
Operating frequency
60 Hz ±1 Hz
Total harmonic current distortion THDi*
<10% @ rated power (with DC-Link choke 4%)
<15% @ rated power (without DC-Link choke or <4%)
Total demand distortion TDD
According to IEEE 519
Nominal motor drive input power rating
5 to 250 HP @ 480 VAC
High potential test voltage
P -> E 2480 VAC for 1 s
Earthing system
TN, TT, IT
Efficiency
≥ 98% at rated voltage and power
Overvoltage category
OV III (IEC 60664-1 / UL 61800-5-1)
Temperature range (operation and storage)
–25°C to +45°C fully operational
+45°C to +70°C derated operation***
–25°C to +85°C transport and storage
Cooling
Internal fan cooling or external fan cooling***
Protection category
IP 00, IP 20
Flammability corresponding to
UL 94V-2
Design corresponding to
UL/IEC 61800-5-1, EN 61800-5-1, CE (LVD2006/95/EC)
Choke: IEC 61558-2-20
SCCR**
100 kA
MTBF (Mil-HB-217F)
>300,000 h @ 45°C/480 V
* System requirements: THDv <2%, line voltage unbalance <1% Note: performance specifications in this datasheet refer to six-pulse diode rectifiers. SCR rectifier front-end will produce different results, depending upon the firing angle of the thyristors. ** External UL-rated fuses required. *** Please check the inlet air flow requirement for cooling, see below in this document and in the user and installation manual. **** Iderated = Inominal * √((70°C-Tamb)/25°C)