Product Information
The Ecosine Flex passive harmonic filters reduce THDi to 10%, optimizing power system efficiency and reliability.
Key Benefits:
- Harmonic Mitigation: Reduces THDi to 10% (15% without a DC-Link), complying with EN 61000-3-12 and IEEE 519.
- Increased Energy Efficiency: Optimizes energy use and minimizes harmonic losses.
- Optimized Design: Compact footprint.
- Ease of Use: Plug-and-play design.
Versatile Applications:
- Equipment with Six-Pulse Input Rectifiers (diode/thyristor)
- Motor Drive Systems (upgrades to low harmonic drives)
- Various Industries (factory automation, water treatment, HVAC, etc.)
FN3446 Series (50 Hz):
- Superior Performance: THDi < 10% (with 4% Ldc) / < 15% (without Ldc or < 4% Ldc).
- Cost-Effective: Economical solution for applications not requiring THDi < 5%.
- Risk Mitigation: Reduces risk of system resonance and downtime.
Technical Specifications
| Parameter | Description |
| Nominal Operating Voltage | 3×380 to 480 VAC ±10% |
| Overload Capacity | 1.6x rated current for 1 minute, once per hour |
| Operating Frequency | 50Hz ± 1 Hz |
| Total Harmonic Current Distortion (THDi)* | < 10% @ rated power (with 4% DC-Link choke) / < 15% @ rated power (without DC-Link choke or < 4%) |
| Total Demand Distortion (TDD) | According to IEEE 519 |
| Rated Input Power of Motor Drive | 4 to 200 kW @ 400 VAC |
| High-Voltage Test Voltage | P to E 2480 VAC for 1 second |
| Grounding System | TN, TT, IT |
| Efficiency | ≥ 98% at rated voltage and power |
| Overvoltage Category | OV III (IEC 60664-1 / UL 61800-5-1) |
| Temperature Range | -25°C to +45°C full operation (except 200 kW)<br>-25°C to +40°C full operation (200 kW only)<br>+45°C to +70°C derated operation (except 200 kW)<br>+40°C to +70°C derated operation (200 kW only)<br>-25°C to +85°C transportation and storage |
| Cooling | Internal/external fan cooling*** |
| Protection Class | IP00, IP20 |
| Flammability | UL 94V-2 |
| Design Conforms to | UL/IEC 61800-5-1, EN 61800-5-1, CE (LVD2006/95/EC); Reactor: IEC 61558-2-20 |
| SCCR | 100 kA** |
| MTBF (Mil-HB-217F) | > 300,000 hours @ 45°C / 400 V |
*For optimal performance: THDv < 2% and line voltage unbalance < 1%.
**External UL-rated fuses required.
***Check required intake airflow (see operating and installation instructions).
**** Iderated = Inominal * √((70°C-Tamb)/25°C) for Tamb > 45°C.
Tiếng Việt