| Model | FX-3500 RCU |
| Manufactures | Mircom |
| Origin | Canada |
| Standards | NFPA 72 Standard; UL, FM Approval |
| Number of Loop | – One onboard SLC/DCL communication circuit that supports up 318 addressable devices/points – Expandable to three SLC/DCL communication circuit sthat supports up to 954 addressable devices/points |
| Display | – 4 x 20 character Liquid Crystal Display (LCD) – Six dedicated hazard zone LED indicators – Four easy to read status queues with selector switchesand LEDs for Alarm, Supervisory, Trouble and BuildingSafety (Formerly Monitor) Input visual indications |
| Standard Features | Reliable and industry proven dedicated releasing powersupply |
| USB port on core board for simple programming and firmware upgrade | |
| Built-in UDACT/DACT for remote monitoring | |
| Enhanced tactile response for operator interface | |
| Easy to read numerical keypad | |
| 10 Ampere (Amp.) Power Supply to satisfy typicalreleasing load requirements | |
| Four Class A/B Notification Appliance Circuits (NAC)rated at 1.5Amp. Each | |
| Resettable auxiliary power supply | |
| Supports up to seven remote annunciators | |
| Accessible multifunction RS-232 port for: – Serial Communication interface |
|
| RS-485 Interface for remote LCD/LED Annunciators andother devices | |
| Optional City Tie/Polarity Reversal module for centralstation monitoring | |
| Bypass adders IPS-2424DS and IPS-4848DS canbe used on this panel, please refer to Optional AdderModules Section | |
| Easy access to all modules for serviceability. | |
| Releasing capability for up to 6 Zones | |
| Supports Pre-Action/Agent Release and Deluge Applications | |
| Built-in strobe synchronization support for Mircom, System Sensor, Gentex and Wheelock protocols | |
| Grouped inputs and outputs | |
| NACs can be configured as Silenceable or Non-Silenceable for both signals and strobes | |
| Group bypass with built-in false alarm prevention technology | |
| Configurable Signal Silence Inhibit, Auto Signal Silence, Two Stage Operation and One-Man Walk Test | |
| Zone Counting | |
| Positive Alarm Sequence | |
| Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble | |
| Two event history logs comprised of a 400 event alarm log for alarm related events and a 400 event general log for all other events | |
| Beam Detector and Duct Detector AP types | |
| Full Windows 10 compatibility | |
| CO-Photo-Heat Combinations | |
| Compatible with INX-10A Addressable Intelligent NAC Expander Panel. | |
| Supports Acclimate smoke detection sensors | |
| Input Voltage | 120VAC 60Hz/240VAC 50Hz, 10A slow blow fuse on secondary of transformer |
| Power Supply Ratings | 29VAC 10A maximum (secondary of transformer) 120VAC 60Hz 3.1Amp (maximum primary of transformer) 240VAC 50Hz 1.57Amp (maximum primary of transformer) Total load not to exceed 10A at 24VDC |
| Battery Type | 24VDC Gel Cell/Sealed lead acid – 10AH to 42AH |
| Battery Charging Capability | 10AH to 42AH |
| NAC Circuits Rating | Power limited / Regulated 24V FWR / 1.5A @ 49C per circuit |
| NAC Circuits Max power allowed | Total 6.0A 1.5A per circuit |
| Dimensions | 26” x 14.5” x 4.2” 66 cm x 36 cm x 11 cm |