Modbus® TCP/IP Specifications
| Specification | Description | |
| Supported Modbus Function Codes | 1: Read Coil Status 2: Read Input Status 3: Read Holding Registers 4: Read Input Registers 5: Force (Write) Single Coil 6: Preset (Write) Single Holding Register |
15: Force (Write) Multiple Coils 16: Preset (Write) Multiple Holding Registers 22: Mask Write Holding Register (Slave Only) 23: Read/Write Holding Registers (Slave Only) |
| Supported Clients | 10 | |
| Supported Servers | MBAP: 5 Encapsulated: 5 |
|
| Command List | Up to 160 fully configurable Client commands | |
| Status Data | Error codes reported individually for each command | |
| Command List Polling | Each command can be individually enabled or disabled; write-only-on-data-change is available |
|
Modbus Serial Specifications
| Specification | Description | |
| Command List | Up to 100 commands per Master port, each fully configurable for Function Code, slave address, register to/from addressing and word/bit count. | |
| Supported Modbus Function Codes | 1: Read Coil Status 2: Read Input Status 3: Read Holding Registers 4: Read Input Registers 5: Force (Write) Single Coil 6: Preset (Write) Single Holding Register |
15: Force (Write) Multiple Coils 16: Preset (Write) Multiple Holding Registers 22: Mask Write Holding Register (Slave Only) 23: Read/Write Holding Registers (Slave Only) |
| Software configurable communication parameters | Baud rate: 110 baud to 115.2 kbps Parity: None, Even, Odd Data Size: 7 or 8 bits Stop bits: 1 or 2 RTS on/off delay: 0 to 65535 milliseconds Modbus RTU mode (binary) with CRC-16 Modbus ASCII mode with LRC error checking Floating Point Data Floating point data movement supported, including configurable support for Enron and Daniel implementations |
|
| Polling of Command List | Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled. | |
| Status Data | Error codes available on an individual command basis. In addition, a slave status list is maintained | |
| Node Address | 1 to 247 (software selectable) | |
| RS Interface | RS232, RS422, and RS485 | |
| Transmit and Receive Buffer Size | 255 byte Transmit character length with 0 to 65535 millisecond delay between each transmitted character | |